Addresses
Contact Us
Products Conforming to RoHS Directive
■ Features
Used to protect power supplies.
Some models are recognized by UL, TÜV.
■ Part number system
■ Dimensions and Packing form
■ Characteristics
Series
Rated
voltage
Part Number
DC spark-over
voltage Vs
Insulation resistance
IR
Electrostatic
capacitance
1kHz-6V max.
C
Surge current
capacity
8/20μsec.
DSANR
AC 125V
DSANR-1
500V (400~600)
100MΩmin.
DC 100V
2pF max.
1000A
DSANR-2
600V (480~720)
DC 250V
DSANR-2A
800V (640~960)
DSANR-2B
1100V (880~1320)
DC 500V
DSANR-4
2400V (1920~2880)
DSANR-6
3600V (2880~4320)
AC 250V
DSANR-3
800V (640~960)
DC 250V
DSANR-3A
1400V (1120~1680)
DC 500V
DSANR-5
3000V (2400~3600)
DC 500V
DSANR-6A
3600V (2880~4320)
DSANR-9
4000V (3200~4800)
DSANR-10B
4500V (3600~5400)
DC 1000V
Series
Rated
voltage
Part Number
DC spark-over
voltage Vs
Surge life
test.
AC
Withstanding
voltage
UL approved
IEC·EN
approved
3)
1)
UL 1414
2)
UL 1449
DSANR
AC 125V
DSANR-1
500V (400~600)
8/20μsec.
100A
500 times
-
-
O
-
DSANR-2
600V (480~720)
-
-
O
-
DSANR-2A
800V (640~960)
-
-
-
-
DSANR-2B
1100V (880~1320)
-
-
-
-
DSANR-4
2400V (1920~2880)
AC 1200V-3sec.
O
-
-
DSANR-6
3600V (2880~4320)
AC 1800V-3sec.
-
-
-
AC 250V
DSANR-3
800V (640~960)
-
-
O
-
DSANR-3A
1400V (1120~1680)
-
-
-
-
DSANR-5
3000V (2400~3600)
AC 1500V-1min.
O
-
O
DSANR-6A
3600V (2880~4320)
AC 1800V-3sec
-
-
O
DSANR-9
4000V (3200~4800)
AC 2000V-1min.
-
-
O
DSANR-10B
4500V (3600~5400)
AC 2000V-1min.
-
-
O
1):
UL Standard UL 1414 File No. E89615(N)
2):
UL Standard UL 1449 File No. E70785(S)
3):
DSANR has received recognition to IEC60384-14 and EN132400 through TÜV.
Report No. J9251508